28 | © 2019 ABB | 1SDH001316R1002 - ECN000086501 - Rev. A Protections | 2 - Standard Protections
2 - Standard Protections
List
The Standard protections available for all Ekip Touch models, are:
Name Type of protection Threshold Time Function
Additional functions
(6)
L Overloads with inverse long-time delay Thermal memory, Pre-alarm threshold
S Short-circuit with adjustable delay
Trip enable, Zone Selectivity, Thermal
memory, Startup enable, Block
S2
(1)
Short-circuit with adjustable delay
Trip enable, Zone Selectivity, Startup
enable, Block
I
(3)
Instantaneous short-circuit Startup enable, Lock
G
(2)(5)
Earth fault with adjustable delay
Trip enable, Zone Selectivity, Startup
enable, Block, Prealarm Threshold
MCR
(4)
Instantaneous short-circuit on circuit-
breaker closing
Monitoring period, Locking
2I Instantaneous short-circuit programmable
Activation function and mode
IU Current unbalance
Trip enable
Neutral Different protection on neutral phase
T Abnormal temperatures
Trip enable
Iinst Instantaneous short-circuit
Harmonic distortion
(7)
Distorted waveforms
Hardware Trip Internal connection errors
Current thresholds
(7)
Control thresholds exceeded Direction of current flow
Further details about the protections are given in document 1SDH001330R1002.
(1)
not available with Trip unit model Ekip G Touch
(2)
not available with LSI version of Trip unit
(3)
can be activated with protection MCR = Disable
(4)
can be activated with protection I = Disable
(5)
if the presence of sensor S.G.R. is activated, the submenu of protection G will be replaced by that of protection Gext, in the Advanced menu; with
Trip unit models Ekip Hi-Touch and Ekip G Hi-Touch, the two protections are available at the same time
(6)
Thermal memory available with curve t=k/I
2
; Zone selectivity available with curve t=k; Block configuration available via Ekip Connect
(7)
the protections do not handle the TRIP, just signaling