ABB | SACE Emax 2
42 | © 2019 ABB | 1SDH001316R1002 - ECN000086501 - Rev. A Settings | 1 - Main settings
Settings
1 - Main settings
Foreword
All the following parameters are available either directly, or from the Settings menu, in the conditions
established by Ekip Touch on the basis of the version and configuration described.
Consult manual 1SDH001330R1002 for any Main settings in the menu which are not described below and
for the Integrative settings (available by accessing the unit by means of a service connector via Ekip Connect
or by communication via system bus):
Circuit-breaker: Hardware Trip, T Protection, Neutral Protection
Phase Sequence
Monitor time
Power Controller
Load Shedding
Network Analyzer
Datalogger
Dual Set
Functions
View
Maintenance
Programmable states
Filters
TAG Name, User data, Clients Page
Led Alive
Supplementary settings for commands, zone selectivity, Wizard
WARNING! changes to the settings must be made in the absence of protection alarms
Configuration
The Circuit breaker-Configuration menu, allowing the presence of the External neutral sensor to be activated,
is available for the 3P CB.
Activation of the configuration with External neutral (3P + N) enables:
histograms of phase Ne in the Histograms page
neutral current measurements
submenu for configuring the Neutral protection (Neutral Protection)
neutral current recording in the case of TRIP
With 3P CB, the parameter is set by default as: 3P.
Ground protection
In the earth Circuit-breaker-Protections menu of the LSIG version of Ekip Touch you can:
activate/deactivate the presence of external sensor S.G.R and relative Gext protection.
activate the presence of Rc Toroid and relative protection.
NOTE: Rc Toroid can be activated if the Measuring Measurements package and Rc version
Rating plug are present; sensor presence in the menu can only be deactivated afterwards by
replacing the installed Rating plug
With Ekip Touch LSIG, the parameter is set by default as: Absent.
Line frequency
Frequency adjustment is performed to set the installation frequency; the choice is between 50 Hz and 60 Hz.
NOTE: the measurements are taken on the basis of the set grid frequency: incorrect configuration
of the parameter may lead to abnormal measurements and protection
Ekip Touch is supplied with the parameter setting that suits the ordered configuration.