ABB | SACE Emax 2
Protections | 8 - Adaptive protections37 | © 2019 ABB | 1SDH001316R1002 - ECN000086501 - Rev. A
9 - Additional protections and functions
Additional protections
Some protections have additional functions which extend their characteristics and performance:
Name Description Protections
Thermal
Memory
Reduced trip time in the case of TRIPs within brief
intervals (protection against cable overheating)
L, S
Zone
selectivity
Additional parameters for managing TRIP commands
between circuit-breakers equipped with the same
function
S, S2, G, D, Gext
Blocks
Blocking of protection on the basis of programmable
events
S, I, G, MCR, S2, D, S(V), S2(V), UV,
OV, VU, UV2, OV2, UP, OP, RP, RQ,
OQ, RV, UF, OF, UF2, OF2, ROCOF,
Gext
Startup
Different threshold of the protection for a limited
time, with activation on the basis of a programmable
monitoring threshold
S, I, G, S2, D, UP, Gext
Additional protections
Installation of certain accessories allows the additional protections to be activated:
Name Type of protection
Threshold
Time Function Additional functions
Gext
Earth fault with current
reading by S.G.R.
external sensor
Trip enable, Zone Selectivity,
Startup enable, Block,
Prealarm Threshold
Rc
Residual current with
corrent reading by
external toroid Rc
Synchrocheck
Synchronism between
two independent voltage
sources or energizing of
a busbar not active
Further details about the protections are given in document 1SDH001330R1002.
Programmable Functions and
Commands
Ekip Touch has eight programmable commands, which activate on the basis of signals or events. Each
command allows the activation function and event monitoring time to be programmed.
Name Description Menu path
External Trip Sends a TRIP command
Advanced - FunctionsRESET Trip TRIP signal reset
Activate SET B Changes the protections set, from Set A to Set B
Energy RESET Resets the energy meters Measurements - Energy
Command YO Sends a command to opening coil YO
Settings - Functions
Command YC Sends a command to closing coil YC
LOCAL Switch On Changes the configuration, from Remote to Local
Settings - Modules
- Functions
Signaling RESET Reset the contacts of the signalling modules