ABB | SACE Emax 2
150 | © 2013 ABB | 1SDH001000R0002 - L7804
Ekip Touch protection release | 20 - Default parameters
Continued from the previous page
The Ekip Hi-Touch and Ekip G Hi-Touch releases have additional protections, provided with the
following default parameters:
Protection/Parameter
Value
(1)
S2 Off; 2 In; 50 ms; Curve: t = k
D Off; 2 In; 200 ms
UV2 Off; 0.9 Un; 5 s
OV2 Off; 1.05 Un; 5 s
UF2 Off; 0.9 fn; 3 s
OF2 Off; 1.1 fn; 3 s
Network Analyzer Off
Harmonic calculation Off
Set A-B Off
The Ekip G Touch and Ekip G Hi-Touch releases have additional protections, provided with the
following default parameters:
Protection/Parameter
Value
(1)
S (v)
Off; 0.6 In; type: Voltage consent; U1 = 100; U2 = 50; U =
100
RV Off; 0.15 Un; 15 s
RQ
Off; K1 = -2; K2 = 2; q01 = 0.1 An; q02= 0.11 An; Vmin =
0.5 Un; 100 s
OQ Off; 1 sn; 1 s
OP Off; 1 sn; 1 s
UP Off; 1 sn; 1 s
The Ekip G Hi-Touch release has additional protections, provided with the following default
parameters:
Protection/Parameter Value
Rocof Off; 0.6 Hz; 600 ms
S2 (v)
Off; 0.6 In; type: Voltage consent; U1 = 100; U2 = 50; U =
100
RQ2
Off; K1 = -2; K2 = 2; q01 = 0.1 An; q02= 0.11 An; Vmin =
0.5 Un; 100 s