ABB | SACE Emax 2
Electrical accessories | 2 - Electrical signalling accessories
233 | © 2013 ABB | 1SDH001000R0002 - L7804
AUP: auxiliary position contacts
The AUP contacts are intended for circuit-breakers in withdrawable version.
They electrically signal the position of a moving part (inserted/test/withdrawn) in relation to the
fixed part in which they are inserted.
These are "switching" contacts and are available, up to a maximum of 10 contacts per circuit-
breaker, in the following configurations:
five standard contacts
five digital signals
five additional standard contacts
five additional digital signals
The following table provides information on the electrical characteristics:
Characteristics Standard Digital signals
Breaking
capacity
DC
24V - 0.1 A
125V 0.5A @ 0ms / 0.3A @ 10ms -
250V 0.3A @ 0ms / 0.15A @ 10ms -
AC
250V
3A cos φ 0,3 -
5A cos φ 0,7 -
5A cos φ 1 -
400V
3A cos φ 1 -
2A cos φ 0,7 -
1A cos φ 0,3 -
Minimum load 50mA @ 24V 1mA @ 5V
AUP: Connections
Further information is available on page 156, or on the site http://www.abb.com/abblibrary/
DownloadCenter/, where the wiring diagram is available 1SDM000091R0001.
104 11 2 124 134 142
141131121111101
124
112
104
134
142
121
111
101
131
141
96
A4
A3
XF
XF
A4
102
102
144
144
S75E/1
24
1
S75E/2
24
1
S75T/1
24
1
S75I/1
42
1
S75I/2
42
1
114
114
122
132
132122
172 182
182
172
164
164
S75I/4
42
1
S75I/3
42
1
S75T/2
24
1
S75E/4
24
1
S75E/3
24
1
194
194
152
152
97
191
181
151
161
171
192
184
154
162
174
151 161 171 181 191
192184174162154
Diagrams 96 - 97
Information on the assembly is available from the web site http://www.abb.com/abblibrary/
DownloadCenter/, in particular with the kit sheet 1SDH001000R0603.