EasyManua.ls Logo

ABB SACE Emax E4.2 - YU: Under-Voltage Coil

ABB SACE Emax E4.2
271 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
ABB | SACE Emax 2
Electrical accessories | 1 - Electrical Control accessories
227 | © 2013 ABB | 1SDH001000R0002 - L7804
YU: under-voltage coil
YU
YO2
D2
D1
The under-voltage coil YU controls the value of the voltage in the circuit to which it is connected.
The coil opens the circuit-breaker when:
the power supply voltage of the coil drops to a value in the range 35%… 70% Un
The under-voltage coil YU can in addition be used for the following purposes:
Release the circuit-breaker remotely using push-buttons of the normally closed type.
Activate the lock when the circuit-breaker is closed (the closing of the circuit-breaker is
allowed only with the under-voltage coil energized).
NOTE: The power supply of the coil must drawn on the supply side of the circuit-
breaker or from an independent source.
The tables listing the available voltages and the electrical characteristics are provided below:
Available voltages (Un)
24V AC/DC
30V AC/DC
48V AC/DC
60V AC/DC
110V…120V AC/DC
220V…240V AC/DC
240V...250V AC/DC
380V…400V AC
415V…440V AC
480V…500V AC
General characteristics YU
Operating limits (Standards
IEC60947-2)
85%...110% Un
Inrush power (Ps) AC= 300VA DC= 300W
Continuous power (Pc) AC= 3.5VA DC= 3.5W
Opening time 50ms
YU: Connections
Further information is available on page 156, or on the site http://www.abb.com/abblibrary/
DownloadCenter/, where the wiring diagram is available 1SDM000091R0001.
A4
X
XV
X
XV
A1
A4
73
D1
D1
D1
YU
D2
D2
D2
-
~
~
+
SO
XB5
1
XB5 2
Diagram 73
Information on the assembly is available from the web site http://www.abb.com/abblibrary/
DownloadCenter/, in particular with the kit sheet 1SDH001000R0504.

Table of Contents