ABB | SACE Emax 2
230 | © 2013 ABB | 1SDH001000R0002 - L7804
Electrical accessories | 2 - Electrical signalling accessories
2 - Electrical signalling accessories
Aux 4Q: auxiliary open-closed
contacts
Q4Q3Q2Q1
43
42
41
33
32
31
23
22
21
13
12
11
The Aux 4Q contacts signal the open/closed state of the circuit-breaker.
These are "switched" contacts and are available in three types:
four standard contacts
four digital signals (low power)
two standard contacts + two digital signals
NOTE: The standard Aux 4Q contacts are always included in the circuit-breakers
The following table provides information on the electrical characteristics:
Characteristics Standard Digital signals
Breaking
capacity
DC
24V - 0.1 A
125V 0.5A @ 0ms / 0.3A @ 10ms -
250V 0.3A @ 0ms / 0.15A @ 10ms -
AC
250V
3A cos φ 0,3 -
5A cos φ 0,7 -
5A cos φ 1 -
400V
3A cos φ 1 -
2A cos φ 0,7 -
1A cos φ 0,3 -
Minimum load 50mA @ 24V 1mA @ 5V
Aux 4Q: Connections
Further information is available on page 156, or on the site http://www.abb.com/abblibrary/
DownloadCenter/, where the wiring diagram is available 1SDM000091R0001.
81
11
14
11
14
11
14
Q/1
12
12
12
22
22
22
Q/2
24
21
24
21
24
21
32
32
32
Q/3
34
31
34
31
34
31
42
42
42
Q/4
44
41
44
41
44
41
XV
A4
X
X
XV
A1
A4
Diagram 81
Information on the assembly is available from the web site http://www.abb.com/abblibrary/
DownloadCenter/, in particular with the kit sheet 1SDH001000R0613.