ABB SACE PR112 - 5.1 Operation mode menu tree

ABB SACE PR112
68 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
ABB SACE SACE PR010/T RH0029002 L2551 16/67
67
5.1 Operation mode menu tree
5.2 Indications on operation
The SACE PR010/T unit can be used only with SACE PR222MP protection releases with test
connectors on the front.
1. Operation mode
8. Select DUT (PR222MP)
1. Test
1. Protections 1. Automatic Start test (select SET ELT)
Create
report
2. Manual 1. Default setting Start test
2. User setting
Set parameters Start test
2. Trip test
Start test
3. Set coil
Start test
4. Reset coil
Start test
2. Reading
1. Currents Read currents
2. Config./Param.
1. DUT
config./param.
1.Manual
parameters
Display DUT configuration and
parameters
2. Electronic
parameters
Display DUT configuration and
parameters
2. Def.
parameters in
PR010/T
1. Only for test
Display DUT default
configuration and parameters
2. Operative
Display DUT default
configuration and parameters
3. Inputs
Read inputs
4. Tripping
parameters
Display tripping parameters
5. Information
Read release identification, SW version and Serial Number
3. Programming
1. Change DUT
config./par.
1. DUT
configuration
Change DUT configuration parameters
2.DUT
parameters
(ELT)
Change DUT protection parameters
2. Download default
parameters
Program DUT with default parameters for normal operation
3. Def. parameters in
PR010/T
1. For test Define DUT protection parameters
2. Operative Define DUT protection parameters
Test connector