ABB SACE SACE PR010/T RH0029002 L2551 21/67
67
7. SACE PR111/P
protection release
7.1 Default setting for automatic PR111/P testing
To test the protection functions in automatic mode, first set the PR111/P protection unit as
follows:
7.2 Operation mode menu tree
Protection
function
Threshold Curve
L 0.4 x In B
S 3 x In
C; I
2
t=k
I 8 x In -
G 0.8 x In B
1° 2° 3° 4° 5° 6° 7°
1. Operation
mode
1. Select DUT
(PR111)
1. Protections 1. Automatic Start test
Create
report
2. Manual Set parameters Start test
2. I inst
protection
Start test
In=
InN=In/2
Nr.
+ -
I1=
xIn
I2=
xIn
I3=
xIn
I4=
xIn
I GL
S
RP 11 1
TEST
TO
P