ABB SACE SACE PR010/T RH0029002 L2551 27/67
67
Manual test example for release PR112/P (vers. "without key").
NOTE: the data indicating the type of CB and protection, the rated current of the
CTs and the Neutral setting are automatically identified by the PR010/T test unit.
In this example, protection function "I" is tested with curve t=k, threshold I3=1.5*In, supplying a
fault current equivalent to 2 times the rated current (In).
10.
PR112/P-A and SACE PR112/PD-A
protection release
1. From the main menu select 1 (Operation mode)
2. Select the PR112 unit with x (PR112)
3. Select the M÷Z version 2 (PR112) (M÷Z)
4. Select the type of activity with 1 (Test)
5. Select the type of test 1 (Protections)
6. Select the test mode 2 (Manual)
7. Select the type of setting used to test
the protections
2 (User setting)
8. Select the protection function to be
tested
3 (I protection test)
9. Using the arrow keys, fill in the page displayed as follows:
10. Select the phase (or phases) on which to simulate the fault current
(L1+L2+L3)
11. Press ENTER to activate fault simulation
I-PROT: t=k, ON
I3: 1.5In => 3000°
t3: Instantaneous
I-f: 2.00In => 4000 A(*)
(*) In this example, the
automatically identified
rating of the current
sensor is 2000 A.