ABB SACE PR112 - Automatic Test of the Release PR123;P

ABB SACE PR112
68 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
ABB SACE SACE PR010/T RH0029002 L2551 60/67
67
7. Release output ZS
8. Rc Test
For example, to perform the automatic test it is necessary to follow the procedure described in the
following table:
A brief description of the various tests will be given below.
15.3.1 Automatic test of the release PR123/P
With the automatic test, a sequence of 13 different tests will be performed at the currents,
voltages, phase shift and phases indicated in the following table:
For example test n° 5 is performed with:
IL1=0,3 In
IL2=IL3= 0 In
V12=V23=V31= 1 Un
Key to be
pressed
Item selected
1 Operation mode
x PR123/P
1Test
1 Automatic test
ENTER
Test
Phase Amplitude Phase shift
Φ
L1 L2 L3 V12 V23 V31 I [In] V[Un]
1
uuuu u u
3.0 1 30°
2
uuuu u u
5.0
3
uuuu u u
10
4
uuuu u u
15
5
uuuu
0.3 1
6
uuuu
3
7
uuuu u u
0.3 1 210°
8
uuuu u u
3
9
uuuu u u
5
10
uuuu u u
10
11
uuuu u u
15
12
uu u
0.0 0.4
13
uu u
1.3