Section 8 System Log Events
GUID-D6DA2BDF-E112-4AFE-8939-A21567B1A859 v1
SAM600 system events
The following
Table 14 lists the system events recorded by SAM600 modules.
Table 14: SAM600 system events
Event name Severity Status Description Required action
Application
initialization
Information ON only Created at several stages
during module startup.
None
Internal Failure Error ON only Created during various
application error
conditions. The module
tries to clear the error once
by restarting. If the error
condition persists the
module will switch-off the
SAM600 application.
If the module
remains in stall
mode, call help
line.
Module restart
initiated
Information ON only Created before the module
enters its restart
sequence.
None
Digital input 1 Information ON /
OFF
Created when the detected
potential of digital input
channel 1 (Test Switch)
changes.
None
Digital input 2, 3,
4
Information ON /
OFF
Created when the detected
potential on one of the
digital input channels 2..4
(Fuse Failure) changes.
None
Topology failure Error /
Information
ON /
OFF
Error log created when the
module detects a topology
error on one of its ports
X101..X104. Information log
created when the topology
error condition vanishes.
In case of an
error log: verify
that physical
connection
between
SAM600
modules is
according to
the
configuration.
Temperature
alarm
Error /
Information
ON /
OFF
Error log created when the
module’s temperature
supervision raises a
temperature alarm.
Information log created
when temperature alarm
condition vanishes.
In case of the
error log, check
temperature in
cubicle.
Command failure Warning ON only Created when the SAM600
module does not
successfully process a
command from the
configuration tool.
If this error
persists and the
configuration
tool fails to
execute a
certain
command, call
help line.
Table continues on next page