2 - 6 WBPEEUI240751C0
AOT-150
AOT-150
Current Out
The AOT-150 block interfaces high level analog output signals.
It supports 16 nonisolated output channels that operate in
current mode (4 to 20 milliamperes). Special output circuitry
allows this block to support redundant I/O electronics.
Maximum error
2
±0.10% of full scale range
Temperature effect (0° to 70°C) ±0.005%/°C
Settling time per channel
(100% step change)
170 msec to 95% of final value
Update rate
3
All channels 18 times per second (56 msec)
Rejection (50-60 Hz)
Normal mode
Common mode
–70 dB
–120 dB
Number of A-to-D converters 16
Full scale resolution 18 b it
BLP fuse (A and B) 1.6 A, 250 V, 5 x 20 mm, fast-acting, low break capacity
(IEC 127-2/II)
IFP/LFP fuse 3.15 A, 250 V, 5 x 20 mm, time-lag, medium break capacity
(IEC 127-2/VI)
Weight
Module
Nonredundant base
Redundant base
1.0 kg (2.2 lb)
1.4 kg (3.1 lb)
1.7 kg (3.7 lb)
NOTES:
1. All specification values are maximums unless stated otherwise.
2. Maximum error includes effects of nonlinearity, repeatability, hysteresis, noise, and quantization error.
3. This is the rate at which the block reads and updates values. The rate at which the values are actually read and become avail-
able to the system depends on the scan cycle of the controller.
SPECIFICATIONS SUBJECT TO CHANGE WITHOUT NOTIC E
Table 2-4. AIN -300 Specific ations
(continued)
Property Characteristic/Value
1
Table 2-5. AOT-150 Specifications
Property Characteristic/Value
1
Output range 4 to 20 mA
Channels 16 nonisolated
Full scale range 18 mA