BLK-100
WBPEEUI240751C0 2 - 7
BLK-100
Blank Block
The BLK-100 block is used to fill empty block positions on a
column. Any empty positions within a column of blocks must
be filled to maintain airflow. Blank blocks are not required,
however, in empty positions at the bottom of a column. The
block supports redundant blank modules.
Maximum error
2
±0.15% of full scale range
Temperature effect (0° to 70°C) ±0.005%/°C
Update rate
3
All channels 16 times per second (63 msec)
Settling time per channel
(100% step change)
50 µsec (resistive load) to 95% of final value
Number of D-to-A converters 1
D-to-A full scale resolution 12 bit
Number of A-to-D converters 1 (readback)
A-to-D full scale resolution 16 bit (readback)
Load compliance
Resistive
Inductive
0to750Ω
600 mH
BLP fuse (A and B) 1.6 A, 250 V, 5 x 20 mm, fast-acting, low break capacity
(IEC 127-2/II)
IFP/LFP fuse 3.15 A, 250 V, 5 x 20 mm, time-lag, medium break capacity
(IEC 127-2/VI)
Weight
Module
Nonredundant base
Redundant base
1.0 kg (2.3 lb)
1.3 kg (2.9 lb)
1.5 kg (3.4 lb)
NOTES:
1. All specification values are maximums unless stated otherwi se.
2. Maximum error includes effects of nonlinearity, repeatability, hysteresis, noise, and quantization error.
3. This is the rate at which the block reads and updates values. The rate at which the values are actually read and become avail-
able to the system depends on the scan cycle of the controller.
SPECIFICATIONS SUBJECT TO CHANGE WITHOUT NOTI CE