WBPEEUI240751C0 PR12 - 1
PR12
DIO-400 Setup
Purpose/Scope
This procedure gives the steps required to set up the DIO-400
block for proper operation. This includes setting jumpers and
switches, and checking for fuses.
Prerequisites
• Completed worksheet WS7.
Parts
None.
To o l s
• Small-tipped, flat-blade screwdriver.
• Needlenose pliers (optional).
Safety Considerations
Procedure
□
1. Set the special operations switch SW2 located on the back
of the I/O module to normal operation.
□
2. Determine the block field power and I/O channel require-
ments. Refer to the appropriate worksheet or any other system
documentation available.
□
3. Set the digital output field power select jumpers J1 and J2
located on the back of the I/O module as appropriate
(Table PR12-1).
10 min.
CAUTION
1. Insure the setting for the digital input fiel d power monitor
jumper DIFP-J2 matches the a ctual field power voltage (IFP or
LFP). Circuit damage will occur if t he LFP voltage is greater
than the voltage setting of jumper DIFP-J2.
87654321
ON
OFF
T00884A