PR12 - 2 WBPEEUI240751C0
Procedure
4. Remove the access cover from the left side of the I/O mod-
ule (Fig. PR12-1).
5. Set the digital input field power select jumper DIFP-J1 as
appropriate (Table PR12-2). Refer to Figure PR12-2 for the
jumper location.
6. Set the digital input field power monitor jumper DIFP-J2 as
appropriate (Table PR12-3). This should correspond to the
IFP/ LFP voltage being used for the digital input channels.
Refer to Figure PR12-2 for the jumper location.
Table PR12-1. D igital Output Field Power Select Jumpers
Field Power
1
J1 J2 Description
IFP Field power from mounting
column bus
LFP Field power from LFP
terminals on base
NOTE:
1. 24 VDC IFP/LFP required when connecti ng to an RLY block.
123 123
123 123
Table PR12-2. D igital Input Field Power Select Jumper
Field Power DIFP-J1
IFP
(24 VDC only)
LFP
123
456
123
456
C1
Table PR12-3. D igital Input Field Power Mo nitor Jumper
Input DIFP-J2
24 VDC
48 VDC
125 VDC
123456
789101112
123456
789101112
123456