WBPEEUI240751C0 PR17 - 1
PR17
CIO-100/110 Cable Connection
Purpose/Scope
This procedure gives the steps required to cable connect an
IISAC01 Analog Control Station to a CIO-100 block. A station
can either connect directly to the CIO-100 block or connect
through a CIO-110 block (Fig. PR17-1).
This procedure only covers CIO-100 and CIO-110 block cable
requirements. Refer to the IISAC01 Analog Control Station
IISAC01 Analog Control StationIISAC01 Analog Control Station
IISAC01 Analog Control Station
instruction for station setup, installation, and cabling
requirements.
Parts
Figure PR17-1. CIO Connection
10 min.
T02043A
CIO-100
CIO-110
CIO-100
IISA C 0 1
CURRENT BYPASS
STATION
IISAC01
ELECTRIC DRIVE/
PULSE POSITIONER
BYPASS STATION
Number Qty Description
NKCS03 1 per station connection CIO-100 to IISAC01 translation cable
NKCS04 1 per station connection CIO-100 to CIO-110 cable
NKCS05 1 per station connection CIO-110 to IISAC01 translation cable