23
34OX_30-1600 rev. B / 1SCC303011M0201
1
A07482
2.5 Description of basic functionality
2.5.1 
2.5.1.1 Source 1 Priority

Switching sequence summary:
An anomaly occurs on the source 1
Override momentary S1 outage delay
Generator start
Source 2 OK
Transfer from S1 to S2 delay
Pre-transfer signal on
Load shed signal on
Pre-transfer S1 to S2 delay
Load shed delay
Transfer switch to the position O (only
with delayed transition I-O-II type and
at least one phase exists in source 1)
Center-Off delay (only with delayed
transition I-O-II type, delay is zero when
all phases are missing in source 1)
Transfer switch to the position II
(source 2)
Post-transfer S1 to S2 delay
Pre-transfer signal off
Retransfer sequence summary:
The source 1 is restored
Transfer from S2 to S1 delay
Pre-transfer signal on
Pre-transfer S2 to S1 delay
Transfer switch to the position O (only
with delayed transition I-O-II type)
Center-off delay (only with Delayed tran-
sition I - O - II type)
Transfer switch to the position I
(source 1)
Load shed signal off
Generator stop delay
Post-transfer S2 to S1 delay
Pre-transfer signal off
Generator stop
Source 2 off