TruONE® ATS, INSTALLATION AND OPERATING INSTRUCTION
1
LCD
Parameters (continued) *Default
Device Parameters (continued)
Time Delays (continued)
Transfer from
S2 to S1
0...120 min
(2* s)
S1 priority: How long the device waits before
transfer sequence back to available S1 begins.
This delay is overridden by 'Override S2 Failure'
in case of S2 failure.
S2 priority: How long the device is keeping the
load on failed S2 although S1 is already
available.
Pre-transfer
S2 to S1
0*...300 s Enabled only when any digital output is
configured as 'Pre-transfer Signal'.
How long the device is keeping pre-transfer
signal activated before transferring from S2
to S1.
Post-transfer
S2 to S1
0*...300 s Enabled only when any digital output is
configured as 'Pre-transfer Signal'.
How long the device is keeping pre-transfer
signal activated after transferring from S2
to S1.
Generator Stop 0...60 min
(5* min)
Enabled only when generator is in use.
Generator cooling time, how long the device is
keeping the generator running without load
after returning to priority source.
Load Shed 0*...60 s Enabled only when any digital output is
configured as 'Load Shed'.
How long before the transfer from priority to
non-priority source the device activates load
shed signal.
Elevator Pre-signal
S1 to S2
0*...60 s Enabled only when any digital output is
configured as 'Elevator pre-signal'.
How long the device is keeping pre-signal
signal activated before transferring from
S1 to S2.
Elevator Post-
signal S1 to S2
0*...60 s Enabled only when any digital output is
configured as 'Elevator pre-signal'.
How long the device is keeping pre-signal
signal activated after transferring from
S1 to S2.
Elevator Pre-signal
S2 to S1
0*...60 s Enabled only when any digital output is
configured as 'Elevator pre-signal'.
How long the device is keeping pre-signal
signal activated before transferring from
S2 to S1.
Elevator Post-
signal S2 to S1
0*...60 s Enabled only when any digital output is
configured as 'Elevator pre-signal'.
How long the device is keeping pre-signal
signal activated after transferring from
S2 to S1.