EasyManua.ls Logo

ABB TTF300 - Operation; Operation Safety Instructions; Hardware Settings and DIP Switches

ABB TTF300
92 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
44 TTF300 FIELD-MOUNT TEMPERATURE TRANSMITTER | OI/TTF300-EN REV. I
10 Operation
Safety instructions
If there is a chance that safe operation is no longer possible,
take the device out of operation and secure it against
unintended startup.
Hardware settings
Devices with HART® from HW-Rev.: 02.00 (corresponds
to Software from SW-Rev.: 03.00 and higher)
HART devices from HW-Rev.: 02.00 do not have DIP switches.The
desired HART profile (HART 7 or HART 5) the write protection are
set via the operating buttons of the LCD display (optional), tools
or HART commands.
Note
Factory setting, unless explicitly ordered otherwise:
HART 7
Write protection OFF
Devices with PROFIBUS PA®, FOUNDATION Fieldbus®,
and HART® to HW-Rev.: 01.07
1
LCD indicator interface
2
DIP switch
Figure 34: DIP switch on the transmitter (not for HART devices from HW-Rev.: 02.00)
The transmitter has two DIP switches that can be accessed via a
hinged cover.
Switch 1 activates the hardware write protection.
Switch 2 supports the FOUNDATION Fieldbus
requirement for a hardware enable for simulation in
accordance with ITK.
For transmitters that support HART 7, switch 2 allows the
desired HART version to be set (HART 5 or HART 7).
DIP switch
Function
1
Local write protection
Off
: Local write protection deactivated
On
: Local write protection activated
2
Enabling the simulation (only with FOUNDATION Fieldbus)
Off
: Simulation blocked
On
: Simulation enabled
Selecting the HART version (only with HART protocol)
Off
: HART 5
On
: HART 7
Note (not for HART devices from HW-Rev.: 02.00)
Factory settings: Both switches ‘OFF’. Local write protection
deactivated and HART 5, unless explicitly ordered HART 7
(HART version) or simulation locked (FOUNDATION Fieldbus).
With PROFIBUS PA devices, Switch 2 must always be in the
OFF’ position.

Table of Contents

Other manuals for ABB TTF300

Related product manuals