58 TTF300 FIELD-MOUNT TEMPERATURE TRANSMITTER | OI/TTF300-EN REV. I
… 10 Operation
… Parameter description HART® (for HART®-devices to SW-Rev.: 01.03)
Menu: Process Alarm
signaling
Underrange:In the event of an error, the current (e.g. 3.6 mA) is output.
• Overrange:In the event of an error, the current (e.g. 22 mA) is output.
Menu: Communication
8 characters
Address range in multidrop mode
Value range:0 to15 (0 means no multidrop mode)
Status (on / off):Switches burst mode on or off
Command # (1, 2, 3, 33):Sets the HART command to be sent cyclically
Number of preambles to be used for sending
Menu: Calibrate
Select the ‘Measured range’ submenu.
Select the ‘Analog Out’ submenu.
… / Calibrate / Measured range
The current reading (PV) is used as the lower range limit (4
mA).
The current reading (PV) is used as the upper range limit (20 mA).
… / Calibrate / Analog Out
Adjusts the current output with a 4 mA setpoint
Value range:3.500 to 4.500 mA
Adjusts the current output with a 20 mA setpoint
to 20.500 mA