TTF300 FIELD-MOUNT TEMPERATURE TRANSMITTER | OI/TTF300-EN REV. I 85
Possible error messages HART® devices from SW-Rev.: 03.00
Note
The listed causes for a device status message correspond to the delivery status.They can be configured freely in Tools in the
Diagnosis/NAMUR configuration” menu, see COM/TTX300/HART interface description.
Range
Device status message
(on the display)
Cause
Remedy
Sensor
Line resistance S1 too high
Maintenance required
Check sensor or replace / repair sensor
Sensor
S1 short
-circuit
Maintenance required
Check sensor or replace / repair sensor
Sensor
S1 Wire break / sensor break
Maintenance required
Check sensor or replace / repair sensor
Sensor
S1 Single
-point trim is active
Check function
Sensor
S1 Two-point trim is active
Check function
Sensor
Line resistance S2 too high
Maintenance required
Check sensor or replace / repair sensor
Sensor
S2 short-circuit
Maintenance required
Check sensor or replace / repair sensor
Sensor
S2 Wire break / sensor break
Maintenance required
Check sensor or replace / repair sensor
Sensor
S2 Single-point trim active
Check function
Sensor
S2 Two
-point trim active
Check function
Sensor
Redundancy:S1 not available
Maintenance Required
Check sensor or replace / repairsensor S1
Sensor
Redundancy:S2 not available
Maintenance Required
Check sensor or replace / repairsensor S2
Sensor
Sensor drift detected
Maintenance required
Check Sensor/ connection / trim / drift parameter
Sensor
Error in the application
Failure
Check sensor connection / check
HART variable mapping
Operation
Diagnostics is simulated
Check function
Terminate / come out of
simulation
Operation
Analog output fixed / simulated
Check function
Terminate / come out of simulation
Operation
Application warning
Check function
Load valid parameter restart (reset) check S1 / S2
Electronics
Electronics temp.
measurement failure
Failure
Restart (RESET) or replace transmitter
Electronics
Electronics temp. out of spec.
Out of specification
Observe spec. ambient temp. range
Electronics
Non
-volatile data defect
Failure
Restart (RESET) or replace
transmitter
Electronics
Non-vol. Memory Write cycles exceeded
Maintenance required
Restart (RESET) or replace transmitter
Electronics
Device not calibrated
Failure
Restart (RESET) or replace transmitter
Electronics
Electronics failure
Failure
Restart (RESET) or replace transmitter
Electronics
Device locked
No Alarm
Reset key value
Process
S1 over sensor range
Maintenance required
Check sensortype use diff. sensor if required
Process
S1 under sensor range
Maintenance required
Check sensortype use diff. sensor if required
Process
S2 over sensor range
Maintenance required
Check sensortype use diff. sensor if required
Process
S2 under sensor range
Maintenance required
Check sensortype use diff. sensor if required
Process
High
limit: Alarm
Out of specification
Verify process or change limit value
Process
Low limit: value Alarm
Out of specification
Verify process or change limit value
Process
High limit: Warning
Out of specification
Verify process or change limit value
Process
Low limit: Warning
Out of specification
Verify process or change limit value
Configuration
Parameterization / config. failure
Failure
Load valid param restart (RESET), reset to factory
Note
If the remedial measures listed for the error message do not improve the status of the device, please consult ABB Service.