84 TTF300 FIELD-MOUNT TEMPERATURE TRANSMITTER | OI/TTF300-EN REV. I
11 Diagnosis / error messages
Possible error messages HART® devices to SW-Rev.: 01.03
Range
Displays the
device
status
Displays the
DIAG.NO.
Cause
Remedy
Sensor
M
66
No sensor
1 detected during redundancy
configuration
Check connection
Sensor
M
67
No sensor
2 detected during redundancy
configuration
Check connection
Sensor
M
68
Sensors exceeded specified drift window
Calibrate sensors
Installation / Configuration
C
71
Reconfiguration is running
Terminate reconfiguration
Operating conditions
F
72
Error in the application
Check configuration, connections; reset to factory
settings
Installation / Configuration
I
74
Analog output adjustment active
Terminate compensation
Installation / Configuration
C
75
Analog output in simulation
Terminate simulation
Operating conditions
S
76
Values overshot
Check parameters:
A) Sensor limits overshot
B) Span is too small
Operating
conditions
S
77
Limit HIGH HIGH
Upper limit value:Alarm
Operating conditions
S
78
Limit LOW LOW
Lower limit value:Alarm
Operating conditions
S
79
Limit HIGH
Upper limit value:Warning
Operating conditions
S
80
Limit LOW
Lower limit value:Warning
Note
If the remedial measures listed for the error message do not improve the status of the device, please consult ABB Service.