TTF300 FIELD-MOUNT TEMPERATURE TRANSMITTER | OI/TTF300-EN REV. I 69
Menu: Communication
Menu / parameter
Description
… /Communication
HART Tag
Measuring point tagging
8 characters
HART Long Tag
Long tag:Unique device label in the plant (from HART 7)
32 characters
Address (Multidrop)
Address range in multidrop mode (HART 5)
Value range:0
to 15 (0 means no multidrop mode)
Address (HART 7)
Address range (HART 7)
Value range:0 to 63 (independent of Current Loop Mode)
Information HART 5:
Address = 0 (Current Loop Mode enabled Multidrop disabled)
Address = 1 to 15 (Current Loop Mode disabled Multidrop enabled)
Current Loop Mode
Only HART 7:
Independent of the address
Enabled = normal operation (output current depends on process variable (PV))
Disabled = Constant output current (like Multidrop HART 5 address 0>)
HART Burstmode
Select the ‘HART Burstmode’ submenu.
HART
Resp.Preambles
Number of preambles to be used for sending
Value range:5
to 20
Find Device
This option helps with finding a device
The HART master sends HART command #73 to search for the device.
Device answeres with HART initialize Command #0 (long addres
s) - if found
Options:
Disabled: no reaction HART command #0
Once:One-time reaction to HART command #0
Continuous:Always switch to HART command #0
HART Revision
Switch the device from HART 5 to HART 7 or from HART 7 to HART 5.
After the change of
HART Revision a device restart is recommended.
Warning:Different drivers for tools for HART 5 and HART 7 required.
… / Communication / HART Burstmode
Status
Off:HART burst operating mode inactive
On:HART burst operating mode active
Command #
Sets the HART command to be sent cyclically
1 Process value: Process value PV
2 current+%: Output current and percentage range
3 Current+Dyn.Vars: Current output and dynamic variables PV, SV, QV, TV
9 Dev.Variables (H7): Device variables - only HART 7
33 Dev.Variables (H5): Device variables - only HART 5
48 Add.Dev.Status: Additional device status