EasyManua.ls Logo

ABB Zenith ZTX Series - Page 20

ABB Zenith ZTX Series
72 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
20
1
Zenith ZTX Series ATS, OPERATION, MAINTENANCE, AND INSTALLATION GUIDE
Feature comparison ZTX controls (DIP)
Lamp
test
l
ON
Off
load
test
ll
ON
Auto
Alarm reset
On
load
test
Bypass
time
delay
Dropout ∆U / ∆f
Manual
retransfer
Generator
stop delay
4 min
30 s
∆U 5% / ∆f 5%
∆U 10% / ∆f 5%
∆U 15% / ∆f 10%
∆U 20% / ∆f 10%
0
1
2
3
4
5
10
15
20
30
S1 Failure
delay
[s]
S1 Return
delay
[min]
On
Off
Auto
config
Start
Ok
Priority
No priority
Source 1
In-phase
monitor
Off
On
AUTO
!
S1 S2
LOAD
l
ll
Source failure detections
No voltage Yes
Undervoltage Yes
Overvoltage Yes
Phase missing Yes
Voltage unbalance Yes
Invalid frequency Yes
Incorrect phase sequence Yes
Features
Controls DIP + keys
LED indications for ATS, S1 and S2 status Yes
Open transition - Standard digital inputs/outputs 0 / 1
Programmable digital inputs/outputs No
Auto config (voltage, frequency, phase system) Yes
Source priority Source 1, No priority
Manual retransfer Yes
In-phase monitor (synchro check) Yes
Genset exercising: on-load, off-load Yes, via Ekip Connect
Load shedding No
Real time clock Yes
Event log Yes, via Ekip Connect
Predictive maintenance No
Harmonics measuring No