PREPARATIONS, INSTALLATION AND TAKING INTO OPERATION
9
To ensure the safe operation of the wallbox, minimum clearances of 50cm must be
kept on all sides of the housing.
In general, the ABL Wallbox is engineered for operation in high ambient tempera-
tures. However, it must be ensured that the maximum operating temperature is not
exceeded through external influences such as direct sunlight or similar.
The wallbox meets the requirements for outdoor installation. Outdoors, the wallbox
should only be installed in covered locations that provide sufficient protection from
weather-related pollution.
Requirements for the power supply
The following standards must always be considered for the electrical installation of the
ABL Wallbox:
All regulatory requirements for low voltage installations according to IEC 60364-1
and IEC 60364-5-52 apply.
Wallbox model variants 3W14A1 and 3W14A2 are designed for connection to and
operation on a rated voltage of 230V 50Hz. The 3W22A2 model variant is intended
for rated voltages of 230V (phase-neutral)or 400V (phase-phase) at 50Hz .
The installation site must offer a sufficiently dimensioned power supply according to
HD 60364-7-722:2012 (see also “Guidelines & Norms” on page 18): This power
supply must be reserved exclusively for the wallbox and must not be used to supply
other electrical devices.
If necessary, a separate power supply must be installed that is intended exclusively
for connecting the wallbox and complies with the general requirements for cabling
and building infrastructure.
Depending on the desired rated power, the installation of the wallbox may need to be
registered with and/or approved by the local electricity grid operator. Please consult the
local regulations of your electricity grid operator.
Cable dimensions must be adjusted according to the desired rated power and other
aspects (such as cable length, material, cabling method etc.). The terminal blocks in
the wallbox are designed for cable dimensions of up to 16mm
2
.
The power supply cables may be installed above or below the wall surface: The
mounting plate provides alternative cable inlets at the top and at the rear.
The power supply for the wallbox must always be protected by its own MCB: Please
always observe current national regulations regarding the selection of circuit-protec-
tion devices.
The wallbox does not have a dedicated ON/OFF switch: If you want to take the wall-
box out of operation, you must always switch the upstream domestic MCB and the
internal RCCBs to the 0 (OFF) position. For the 3W14A2 and 3W22A2 model vari-
ants, you also have the option of deactivating the charging function via the integrat-

Other manuals for ABL eMH3

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABL eMH3 and is the answer not in the manual?

ABL eMH3 Specifications

General IconGeneral
CategoryBattery Charger
Connector TypeType 2
Number of Charging Points1
Protection RatingIP54
Charging Current32 A
Input Voltage400 V AC
Protection ClassI
Output Voltage400 V AC
Output Current32 A
Operating Temperature-25°C to +50°C
Cooling MethodNatural Convection
ModeleMH3
Protection FeaturesOvercurrent protection, overvoltage protection, short circuit protection
Charging Powerup to 22 kW