B.5 DESCRIPTION OF PI PARAMETERS
P10 TB-13A FUNCTION SELECT
12 KEYPAD SETPOINT: This option has been added so that the ! and " buttons on the front of
the drive can be used as the PI setpoint reference source. Closing TB-13A to TB-2 will enable
the PI mode and the ! and " buttons can be used to select the desired process setpoint.
P11 TB-13B FUNCTION SELECT
09 KEYPAD SETPOINT: This option has been added so that the ! and " buttons on the front of
the drive can be used as the PI setpoint reference source. Closing TB-13A to TB-2 will enable
the PI mode and the ! and " buttons can be used to select the desired process setpoint.
P12 TB-13C FUNCTION SELECT
10 KEYPAD SETPOINT: This option has been added so that the ! and " buttons on the front of
the drive can be used as the PI setpoint reference source. Closing TB-13A to TB-2 will enable
the PI mode and the ! and " buttons can be used to select the desired process setpoint.
P61 PI MODE
This parameter must be set to match the type of system and the type of feedback signal used. A direct
acting system is one that requires the motor speed to increase as the feedback signal decreases, while
a reverse acting system requires the motor speed to decrease as the feedback signal decreases.
01 DISABLED Disables the PI function to allow standard drive operation.
02 NORMAL 4-20 mA Enables the PI function for a direct acting system with a 4-20 mA
feedback signal.
03 NORMAL 0-10 VDC Enables the PI function for a direct acting system with a 0-10 VDC
feedback signal.
04 REVERSE 4-20 mA Enables the PI function for a reverse acting system with a 4-20 mA
feedback signal.
05 REVERSE 0-10 VDC Enables the PI function for a reverse acting system with a 0-10 VDC
feedback signal.
When PI is disabled, the drive will operate in an OPEN LOOP mode, responding directly to a speed
reference source selected using STANDARD SPEED SOURCE (Parameter 05) or terminals TB-13A,
13B, and/or 13C).
P62 MIN FEEDBACK
This parameter should be set to the value of the process variable that corresponds to the minimum
transducer feedback signal (0 VDC or 4 mA). See the example below.

Table of Contents

Other manuals for AC Tech SCF SERIES

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the AC Tech SCF SERIES and is the answer not in the manual?

AC Tech SCF SERIES Specifications

General IconGeneral
BrandAC Tech
ModelSCF SERIES
CategoryController
LanguageEnglish