FACTORY
NO. PARAMETER NAME RANGE OF ADJUSTMENT
DEFAULT
(NOTE 1)
01 LINE VOLTAGE HIGH (01), LOW (02) HIGH (01)
02 CARRIER FREQUENCY 4kHz (01), 6 kHz (02), 8 kHz (03), 10 kHz (04) 6 kHz (02)
03 START METHOD NORMAL (01), START ON POWER UP (02), NORMAL (01)
START WITH DC BRAKE (03),
AUTO RESTART WITH DC BRAKE (04),
FLYING RESTART 1 (05), FLYING RESTART 2 (06),
FLYING RESTART 3 (07)
04 STOP METHOD COAST (01), COAST WITH DC BRAKE (02), COAST (01)
RAMP (03), RAMP WITH DC BRAKE (04)
05 STANDARD SPEED KEYPAD (01), PRESET #1 (02), KEYPAD (01)
SOURCE 0-10 VDC (03), 4-20 mA (04)
06 TB-14 OUTPUT NONE (01), RUN (02), FAULT (03), NONE (01)
13 TB-15 OUTPUT INVERSE FAULT (04), FAULT LOCKOUT (05), NONE (01)
AT SET SPEED (06), ABOVE PRESET #3 (07),
CURRENT LIMIT (08), AUTO SPEED (09),
REVERSE (10)
08 TB-30 OUTPUT NONE (01), 0-10 VDC FREQ (02), NONE (01)
2-10 VDC FREQ (03), 0-10 VDC LOAD (04),
2-10 VDC LOAD (05)
09 TB-31 OUTPUT NONE (01), 0-10 VDC LOAD (02), NONE (01)
2-10 VDC LOAD (03), DYNAMIC BRAKING (04)
10 TB-13A FUNCTION NONE (01), 0-10 VDC (02), 4-20 mA (03), NONE (01)
SELECT PRESET SPEED #1 (04), RUN REVERSE (05),
START REVERSE (06), EXTERNAL FAULT (07),
REMOTE KEYPAD (08), DB FAULT (09),
AUXILIARY STOP (10), ACCEL/DECEL #2 (11)
11 TB-13B FUNCTION NONE (01), 0-10 VDC (02), 4-20 mA (03), NONE (01)
SELECT PRESET SPEED #2 (04), DECREASE FREQ (05),
JOG FORWARD (06), JOG REVERSE (07),
AUXILIARY STOP (08)
14.0 PARAMETER MENU
NOTE 1: Factory defaults are shown for a 60 Hz base frequency. See Parameter 48 for 50 Hz base frequency.