Chapter 4 Command Set 4-85
Chapter 4
4014D
$AA7(data_C)(data_D)
Example command: $137+000.00+200.00(cr)
response: !13(cr)
The module is configured for ±20 mA input current range.
Previously the module executed the command
$136+04.000+20.000, which ordered the module with address
13 to map data from +4.0 mA and +20.0 mA. The current
command defines the range (0 and 200) to which these values
will be mapped to. From now on, if the input signal is 12 mA,
then the output will be 100.00. Notice that the addressed
module will also update the input limit values to +04.000 mA
and +20.000 mA for the previous command
$136+04.000+20.000. Input signals out of this range will cause
invalid output data.
Example command: $017+100.00-100.00(cr)
response: !01(cr)
The module is configured for a ±150 mV input voltage range
and already executed command $016-100.00+100.00. The
current command requests the module at address 01 to map
data from the earlier specified -100.00 mV and +100.00 mV to
the range +100.00 and -100.00. Therefore, if an input signal
of 50 mV is received, then the output will be -50.00. Notice
that the addressed module will also update the input limit value
to be -100.000 mV and +100.00 mV because of the previous
command $136-100.00+100.00. Input signals out of this range
will cause invalid output data.