2-10 ADAM 4000 Series User's Manual
Installation Guideline
Changing Baud rate and Checksum
Baud rate and checksum settings have several things in common:
They should be the same for all modules and host computer.
Their setting can only be changed by putting a module in the INIT*
state.
Changed settings can only take effect after a module is rebooted
To alter baud rate or checksum settings you must perform the following
steps:
Power on all components except the ADAM Module.
Power the ADAM module on while shorting the INIT* and GND
terminals (See Figure 2-3).
Wait at least 7 seconds to let self calibration and ranging take effect.
Configure the checksum status and/or the baud rate.
Switch the power to the ADAM Module OFF.
Remove the grounding of the INIT* terminal and power the module on.
Wait at least 7 seconds to let self calibration and ranging take effect.
Check the settings (If the baud rate has changed, the settings on the host
computer should be changed accordingly).
Figure 2-3
Grounding the INIT* Terminal