I/O Modules
3-28 ADAM 4000 Series User's Manual
Channel 8
Input Type Thermocouple
T/C type and Temperature
Range
J 0 ~ 760 C
K 0 ~ 1000 C
T -100 ~ 400 C
E 0 ~ 1000 C
R 500 ~ 1750 C
S 500 ~ 1750 C
B 500 ~ 1800 C
Isolation Voltage
3000 V
DC
Fault and overvoltage
protection
Withstands over voltage up to +/- 35 V
Sampling Rate 10 sample/sec (total)
Input Impedance 20 MΩ
Accuracy +/- 0.1% or better
Power Consumption 0.5 W
I/O Conne ctor Type
10-pin plug-terminal
Technical specification of ADAM-4018+
http://www.advantech.com/ ! "service & support"
! search "ADAM-4018+"