Chapter 4 Command Set 4-45
%AANNTTCCFF
Response !AA(cr) if the command is valid.
?AA(cr) if an invalid parameter was entered or if the INIT*
terminal was not grounded when attempting to change baud
rate or checksum settings.
There is no response if the module detects a syntax error or
communication error or if the specified address does not exist.
! delimiter character indicates a valid command was received.
? delimiter character indicates the command was invalid
AA (range 00-FF) represents the 2-character hexadecimal
address of an analog input module.
(cr) is the terminating character, carriage return (0Dh)
Example command: %2324050600(cr)
response: !24(cr)
The ADAM-4011 module with address 23h is configured to a
new address of 24h, an input range ±2.5 V, baud rate 9600,
integration time 50 ms (60 Hz), engineering units data format
and no checksum checking or generation.
The response indicates that the command was received.
Wait 7 seconds to let the new configuration settings take effect
before issuing a new command to the module.
NOTICE: An analog input module requires a maximum of 7 seconds to
perform auto calibration and ranging after it is reconfigured. During this
time span, the module cannot be addressed to perform any other actions.
NOTICE:
All configuration parameters can be changed dynamically,
except checksum and baud rate parameters. They can only be altered
when the INIT* terminal is grounded. (Refer to Baud rate and Checksum
configuration in Chapter 2,
for the correct procedure)