Chapter 4 Command Set 4-47
Input Range Code (Hex) Input Range for 4013
20 Platinum, -100
o
to 100
o
C, α=0.00385
21 Platinum, 0
o
to 100
o
C, α=0.00385
22 Platinum, 0
o
to 200
o
C, α=0.00385
23 Platinum, 0
o
to 600
o
C, α=0.00385
24 Platinum, -100
o
to 100
o
C, α=0.003916
25 Platinum, 0
o
to 100
o
C, α=0.003916
26 Platinum, 0
o
to 200
o
C, α=0.003916
27 Platinum, 0
o
to 600
o
C, α=0.003916
28 Nickel, -80
o
to 100
o
C
29 Nickel, 0
o
to 100
o
C
Input Rage Code (Hex) Input Range for ADAM-4016
00 ±15 mV
01 ±50 mV
02 ±100 mV
03 ±500 mV
06 ±20 mA
Table 4-2 Baud Rate Codes
Baud Rate Code (hex) Baud Rate
03 1200 bps
04 2400 bps
05 4800 bps
06 9600 bps
07 19.2 kbps
08 38.4 kbps
4011, 4011D, 4012, 4013, 4015, 4016,
4017, 4017+, 4018, 4018+, 4018M, 4019