EasyManuals Logo

Advantech Adam-4016 User Manual

Advantech Adam-4016
398 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #158 background imageLoading...
Page #158 background image
4-74 ADAM 4000 Series User's Manual
$AAS1
Name Reload Default Calibrating Parameter
Description Reload factory default calibrating parameter to overwrite current
calibrating parameter
Syntax $AAS1(cr)
$ is a delimiter character.
AA (range 00-FF) represents the 2-character hexadecimal
address of the analog input module which is to be reloaded.
S1 represents the reload calibrating parameter system command.
(cr) is the terminating character, carriage return (0Dh).
Response !AA(cr) if the command was valid.
?AA(cr) if an invalid operation was entered.
There is no response if the module detects a syntax error or
communication error or if the specified address does not exist.
! delimiter character indicates a valid command was received.
? delimiter character indicates the command was invalid.
AA (range 00-FF) represents the 2-character hexadecimal
address of the analog input module.
(cr) represents terminating character, carriage return (0Dh).
4015

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Advantech Adam-4016 and is the answer not in the manual?

Advantech Adam-4016 Specifications

General IconGeneral
BrandAdvantech
ModelAdam-4016
CategoryOther
LanguageEnglish

Related product manuals