Chapter 4 Command Set 4-83
Chapter 4
4014D
$AA6(data_A)(data_B)
Example command: $136+04.000+20.000(cr)
response: !13(cr)
The module is configured for a ±20 mA input current range.
The command orders the module at address 13 to change its
analog input range from +04.000 mA to +20.000 mA. The
addressed module stores these values in a buffer and will only
update the high/low limit value of the input current range when
command $137(data_C)(data_D) is executed (see command
$AA7(data_C)(data_D)).
Example command: $016-100.00+100.00(cr)
response: !01(cr)
The module is configured for a ±150 mV input range. The
command orders the module at address 01 to change its analog
input range from -100.00 mV to +100.00 mV. The addressed
module stores these values in a buffer and will only update the
high/low limit value of the input current range when command
$017(data_C)(data_D) is executed.