Appendix A Technical Specifications A-3
Appendix A
Table A-2 ADAM-4011 Range Accuracy for Thermocouple
Input Range
Code (Hex)
Input Range Typical
Accuracy
Maximum
Error
Units
0E J thermocouple 0 to
760 C
0.5 0.75 C
0F K thermocouple 0 to
1000 C
0.5 0.75 C
10 T thermocouple -100 to
400 C
0.5 0.75 C
11 E thermocouple 0 to
1000 C
0.5 0.75 C
12 R thermocouple 500 to
1750 C
0.6 1.5 C
13 S thermocouple 500 to
1750 C
0.6 1.5 C
14 B thermocouple 500 to
1800 C
1.2 2.0 C