Command Set
4-22 ADAM 4000 Series User's Manual
Command Syntex
Command
Response
Syntex
Command Description
Command
Example
Command
response
Example
$AAM(cr) !AA(name)(cr)-
name : 4017P
The command request the
module at address AA to
return the module name
$03M(cr) !034018P(cr)
$AA7CiRrr(cr)C :
channeli : 0 ~ 7R :
Rangerr : Range
code
!AA(cr) R : Range
rr : +/-0~20mA: 0x06
+/-4~20mA: 0x07
J type : 0x0e
K type : 0x0f
T type : 0x10
E type : 0x11
R type : 0x12
S type : 0x13
B type : 0x14
$057R0EW-
5C6(cr)
!05(cr)
$AA8Ci(cr)i= 0 ~ 7
(channel number)
!AACiRrr(cr) Get the input type of the
assignment channel
$058C6(cr) !05C6R08(cr)
$AAXnnnn(cr)nnnn:
0000 ~ 9999unit:
0.1sec
!AA(cr) Set communication WDT value
form 0000 ~ 9999 (if value is
0000 the communication WDT
function will be disable)
$05X0030(-
cr)
!05(cr)
$AAY(cr) !AAnnnn(cr)n-
nnn: 0000 ~
9999
Get communication WDT
setting value
$05Y(cr) !050030(cr)
$AAB(cr) !AANN(cr)NN:
00 ~ FFbit
value : 0 for
normal, 1 for
open wire
Get the channel operating
statusWhen bit value is 0, it
mean this channel is in normal
operating, when bit value is 1,
it mean this channel is
opening wire
$12B(cr) !1205(cr)05
mean channel
0 and 2 is
open
$AA3(cr) >snnnn.n(cr)s:
+ or -n: digit
Get the CJC current value $063(cr) >+0035.8(cr)
$AA9SNNNN(cr)
S: + or -NNNN: 0000
~ FFFF
!AA(cr) Calibrates an analog input
module to adjust for offset
errors of its CJC sensors
$079+0500-
(cr)
!07(cr)