D-4 ADAM-5510/P31
Performance
D.1.1.2 ADAM-5017
Table D-2: ADAM-5017 channel response time
Note 1: Each ADAM-5017 module updates all of its active
channels concurrently every 100 ms. This updating
process takes 4.8 ms for the entire module.
Test Function Block
ADAM-5510/P31
ADAM-5056
Digital Output
Oscilloscope
ADAM-5013
Analog Input
ADAM-5056
Digital Output
Input channels Response time(ms) Remark
1
0.368
2
0.429
3
0.463
4
0.563
5
0.631
6
0.699
7
0.771
8
0.831
9
0.919
10
0.985
11
1.059
16
1.389
17
1.449
18
1.517
24
1.939