Switch-mode power supply AC2000 N1 / DC2000 N1 / AC3000 N1 / DC3000 N1 - Operating instructions
80001533 EFE en Page 16 of 41
Monitoring Basic settings
......................................................... Description of the monitoring:
( section 6)
- Mains undervoltage with switch-off, self-
acknowledging
- Mains overvoltage with switch-off,
self-acknowledging
- Overtemperature
( Type overview, section 4.2)
- DC undervoltage
( Type overview section 4.2)
- DC overvoltage
( Type overview section 4.2)
Displays ........................................... - Mains input and operation, displayed by
LEDs
- Internal/external U setpoint, displayed by
LED
- U
Out
and I
Out
, displayed via LCD digital
display
- Overvoltage and undervoltage
output monitoring, displayed by LEDs
- Overtemperature monitoring, displayed by
LED
- Deviation monitoring between actual value
and setpoint, displayed by LED
External functions - ......................... Collective fault signal via potential-free relay
contact
- ON/OFF via external potential-free contact
- External sensing line output voltage U
Out
,
output current I
Out
- External setpoint specification 0 to 4 V
for U
Out
, with LED display
- External setpoint specification 0 to 4 V
for I
Out
(available on request, internal device
setting)
- Selectable setpoint specification from four
different preset setpoints (trickle charging,
heavy charging,
NEA, manual charging)
Parallel operation, Number .............. unlimited, load sharing approx. 10 % of the
nominal system current
Type ................................................. 19" full insert
Installation position .......................... Horizontal
Distance between devices ............... 3 U (134 mm), air baffle required between the
devices
Protection class ............................... IP 20
Protection class ............................... Protection class 1
Cooling ............................................. Air self-cooling
Sound pressure level ....................... 30 dB(A) (at a distance of 1 m)
according to EN ISO 3744

Table of Contents