Environmental conditions
Operation ........................................ IEC 60721 Part 3-3
Class 3K22 / 3Z1 / 3B2 / 3C2 / 3S6 / 3M11
Condensation not permitted.
Ambient temperature Dependent on type
( section 4.2 Type overview and section 4.3
Derating).
Transportation .................................. IEC 60721 Part 3-2
Class 2K12 / 2B2 / 2C2 / 2S5 / 2M4
Protected in suitable packaging.
-25 °C to 70 °C
Storage ............................................ IEC 60721 Part 3-1
Class 1K21 / 1B2 / 1C2 / 1S12 / 1M11
Condensation not permitted.
-25 °C to 55 °C
Installation altitude ........................... up to 1000 m above sea level, above that
power reduction
Degree of soiling .............................. 2
Mechanical strength
and vibration resistance ................... EN 60068-2-6
Front panel ....................................... Anodized aluminium
Chassis ........................................... galvanized sheet steel
Mounting in the cabinet .................... 4x M6 screws
(not included in the scope of delivery)
MTBF according to .......................... MIL-HDBK-217 223,178 h at 25 °C
Connection technology (* = included in the scope of delivery)
Mains connection X1........................ Plug-in terminal, screw-fastened*
up to 4 mm² (plastic-insulated wire end
ferrule)
max. 0.6 Nm
DC output X2 (U
Out
) .......................... Connection threaded bolt M8 with nuts*
max. 6 Nm
Protective conductor ........................ Connection threaded bolt M6 with nut*
max. 4.4 Nm
Signal interface X11 ......................... Plug-in and screw-on terminal block*, 14-pole
up to 0.5 mm² (plastic-insulated wire end
ferrule)
up to 1.5 mm² (bare wire end ferrule)
Signal interface X12 ......................... Plug-in and screw-on terminal block*, 10-pole
up to 0.5 mm² (plastic-insulated wire end
ferrule)
up to 1.5 mm² (bare wire end ferrule)