4 TECHNICAL DATA
4.1 General technical data
Inrush current ................................... Current consumption input current
Required mains fuse gL .................. 16 A
Input fuse ......................................... Internal HRC fuse
Characteristic curve ......................... IU characteristic curve according to DIN
41772
Emitted interference ......................... according to EN 61000-6-3
- Conducted interference ................. according to EN 61204-3 for residential,
commercial and light-industrial environments
- Radiation ....................................... according to EN 61204-3 for residential,
commercial and light-industrial environments
Interference immunity ..................... according to EN 61000-6-2 for industrial
environments
- Enclosure ....................................... ESD test acc. to EN 61000-4-2:
6 kV contact
8 kV air discharge
HF field acc. to EN 61000-4-3:
10 V/m (80 MHz - 1 GHz)
- Power cables ................................. Burst test acc. to EN 61000-4-4:
2 kV
Surge test acc. to EN 61000-4-5:
2 kV conductor against ground
1 kV conductor against conductor
- Control cables ................................ Burst test acc. to EN 61000-4-4:
2 kV
Surge test acc. to EN 61000-4-5:
2 kV conductor against ground
Functional extra-low voltage ............ with safe isolation according to IEC 60364-4-
41
Isolation (1 sec.) .............................. Input – Output: 2,83 kV DC
Input – Case: 2,83 kV DC
Output – Case: 0,71 kV DC
Remote signalling – Output: 1,75 kV DC
Dynamic behaviour .......................... ± 5 % with sudden load changes between
10 %-90 %-10 % rated output current (settling
time t 1 ms)
Short-circuit behaviour .................... permanent short-circuit proof,
limited short-circuit current
( type overview section 4.2)