EasyManua.ls Logo

AEG AC2000 N1 - 4 Technical Data; General Technical Data

AEG AC2000 N1
41 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Switch-mode power supply AC2000 N1 / DC2000 N1 / AC3000 N1 / DC3000 N1 - Operating instructions
80001533 EFE en Page 15 of 41
4 TECHNICAL DATA
4.1 General technical data
Inrush current ................................... Current consumption input current
Required mains fuse gL .................. 16 A
Input fuse ......................................... Internal HRC fuse
Characteristic curve ......................... IU characteristic curve according to DIN
41772
Emitted interference ......................... according to EN 61000-6-3
- Conducted interference ................. according to EN 61204-3 for residential,
commercial and light-industrial environments
- Radiation ....................................... according to EN 61204-3 for residential,
commercial and light-industrial environments
Interference immunity ..................... according to EN 61000-6-2 for industrial
environments
- Enclosure ....................................... ESD test acc. to EN 61000-4-2:
6 kV contact
8 kV air discharge
HF field acc. to EN 61000-4-3:
10 V/m (80 MHz - 1 GHz)
- Power cables ................................. Burst test acc. to EN 61000-4-4:
2 kV
Surge test acc. to EN 61000-4-5:
2 kV conductor against ground
1 kV conductor against conductor
- Control cables ................................ Burst test acc. to EN 61000-4-4:
2 kV
Surge test acc. to EN 61000-4-5:
2 kV conductor against ground
Functional extra-low voltage ............ with safe isolation according to IEC 60364-4-
41
Isolation (1 sec.) .............................. Input – Output: 2,83 kV DC
Input – Case: 2,83 kV DC
Output – Case: 0,71 kV DC
Remote signalling – Output: 1,75 kV DC
Dynamic behaviour .......................... ± 5 % with sudden load changes between
10 %-90 %-10 % rated output current (settling
time t 1 ms)
Short-circuit behaviour .................... permanent short-circuit proof,
limited short-circuit current
( type overview section 4.2)

Table of Contents