19
English
COOLING CAPACITY
FCX 32
The cooling capacities in the table must be multiplied by the following factors:
MOD. FCX 32 FCX 34
Maximum speed
total capacity
1,00 1,17
sensible capacity
1,00 1,12
Medium speed
total capacity
0,86 1,02
sensible capacity
0,81 0,94
Low speed
total capacity
0,65 0,85
sensible capacity
0,58 0,76
TOTAL COOLING CAPACITY [W] SENSIBLE COOLING CAPACITY [W]
Wet bulbe air temperature [°C] Dry bulbe air temperature [°C]
Water temp.
Inlet [°C] t 15 17 19 21 23 21 23 25 27 29 31
3 1303 1866 2512 3148 1134 1368 1612 1817 2004 2184
4 1618 2281 2921 1351 1604 1851 2055 2253 2438
5 5 1415 2026 2728 3419 1231 1485 1750 1973 2176 2371
6 1231 1793 2502 3228 3968 1088 1360 1623 1881 2090 2292
7 1064 1556 2246 3010 3770 997 1222 1493 1753 2001 2210
3 1587 2241 1347 1593 1831 2029 2220 2409
4 1407 2013 2693 1230 1477 1733 1954 2153 2340
6 5 1236 1780 2491 3189 3924 1103 1366 1623 1867 2076 2272
6 1056 1552 2219 2984 3732 974 1236 1494 1755 1989 2193
7 960 1332 1964 2759 3528 906 1104 1368 1630 1895 2106
3 1363 1989 1219 1479 1726 1928 2120 2313
4 1205 1758 2456 3138 1095 1355 1604 1849 2054 2246
7 5 1069 1552 2210 2947 3681 987 1240 1488 1750 1973 2174
6 939 1341 1956 2733 3489 878 1114 1377 1630 1884 2090
7 871 1152 1705 2456 3272 817 997 1248 1501 1759 2004
3 1174 1723 2403 1084 1349 1593 1827 2022 2212
4 1056 1523 2193 2895 990 1233 1476 1744 1950 2149
8 5 942 1337 1938 2693 3438 878 1114 1372 1625 1868 2072
6 841 1161 1710 2448 3228 785 990 1255 1501 1755 1989
7 1012 1490 2170 2997 727 906 1120 1382 1636 1896
3 1042 1475 2162 981 1221 1477 1722 1921 2115
4 952 1320 1912 2649 881 1114 1357 1616 1848 2046
9 5 843 1152 1688 2413 3182 764 1001 1248 1492 1752 1970
6 1009 1472 2158 2959 695 881 1128 1386 1632 1882
7 911 1275 1881 2693 635 817 1003 1263 1261 1771
3 942 1264 1872 875 1089 1348 1591 1819 2013
4 847 1131 1653 2386 3112 774 997 1240 1491 1743 1948
10 5 1014 1447 2113 2914 663 891 1134 1376 1624 1864
6 900 1271 1864 2680 622 785 1008 1266 1513 1755
7 1104 1623 2378 542 727 906 1145 1389 1638
3 839 1095 1600 2320 769 983 1224 1474 1716 1914
4 1007 1420 2078 2851 661 891 1109 1359 1615 1844
11 5 909 1258 1832 2636 574 778 1010 1254 1503 1749
6 1102 1618 2355 512 695 895 1148 1392 1634
7 963 1398 2078 448 635 817 1015 1274 1524
3 992 1363 2035 661 880 1091 1349 1587 1813
4 904 1212 1793 2579 546 783 1003 1242 1491 1737
12 5 1087 1583 2316 483 667 902 1141 1379 1622
6 971 1390 2030 419 605 788 1021 1274 1517
7 1209 1789 347 542 727 911 1159 1405
3 891 1172 1739 552 774 987 1210 1472 1709
4 1063 1534 2267 452 672 898 1114 1359 1610
13 5 971 1352 1995 391 574 792 1019 1260 1503
6 1198 1754 321 512 695 911 1158 1394
7 1042 1534 238 448 635 817 1033 1291
NB: Values of capacity in bold face refer to nominal value.
Values of sensible capacity higher than values of total capacity mean that cooling is without dehumidification. In this case consi-
der only the values of sensible capacity.

Other manuals for AERMEC FCX

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the AERMEC FCX and is the answer not in the manual?

AERMEC FCX Specifications

General IconGeneral
BrandAERMEC
ModelFCX
CategoryHousehold Appliance
LanguageEnglish

Related product manuals