EasyManuals Logo

AERMEC FCX User Manual

AERMEC FCX
72 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #18 background imageLoading...
Page #18 background image
20
English
COOLING CAPACITY
FCX 42
The cooling capacities in the table must be multiplied by the following factors:
MOD. FCX 42 FCX 44
Maximum speed
total capacity
1,00 1,31
sensible capacity
1,00 1,20
Medium speed
total capacity
0,82 1,11
sensible capacity
0,77 0,99
Low speed
total capacity
0,68 0,87
sensible capacity
0,59 0,75
TOTAL COOLING CAPACITY [W] SENSIBLE COOLING CAPACITY [W]
Wet bulbe air temperature [°C] Dry bulbe air temperature [°C]
Water temp.
Inlet [°C]
t 15 17 19 21 23 21 23 25 27 29 31
3 2871 2336 2730 3088 3401 3715
4 2491 3516 4551 2149 2550 2942 3279 3602 3907
5 5 2156 3110 4241 5329 1920 2332 2752 3134 3468 3791
6 1808 2717 3825 5010 6191 1648 2113 2530 2955 3320 3653
7 1602 2278 3368 4635 5854 1544 1850 2298 2737 3155 3507
3 2491 3497 2131 2542 2918 3240 3552
4 2166 3103 4194 1939 2349 2755 3112 3437 3749
6 5 1879 2730 3832 4963 6126 1706 2143 2554 2962 3303 3628
6 1563 2343 3426 4626 5816 1496 1908 2337 2754 3150 3489
7 1457 1924 2962 4204 5460 1402 1685 2094 2528 2951 3339
3 2146 3071 1929 2336 2730 3076 3393 3702
4 1882 2742 3825 4898 1740 2160 2553 2941 3275 3592
7 5 1621 2375 3400 4579 5751 1523 1944 2343 2760 3133 3465
6 1415 2014 2987 4223 5423 1355 1679 2138 2558 2960 3322
7 1321 1689 2556 3471 5048 1260 1544 1878 2338 2754 3163
3 1850 2704 3761 1740 2136 2539 2909 3228 3540
4 1647 2382 3381 4523 1564 1948 2357 2754 3108 3429
8 5 1482 2040 3013 4185 5357 1334 1751 2160 2561 2958 3298
6 1279 1737 2601 3748 5010 1216 1507 1940 2353 2761 3151
7 1518 2195 3297 4616 1118 1402 1695 2140 2559 2975
3 1644 2324 3342 1571 1934 2334 2739 3064 3379
4 1482 2033 2987 4128 1388 1753 2166 2554 2936 3267
9 5 1266 1782 2588 3741 4954 1169 1557 1962 2369 2758 3131
6 1515 2233 3297 4588 1074 1355 1733 2172 2565 2964
7 1386 1859 2846 4109 976 1260 1540 1932 2362 2760
3 1482 1995 2936 1398 1746 2135 2536 2899 3215
4 1312 1769 2581 3683 4869 1203 1581 1961 2357 2750 3100
10 5 1563 2246 3284 4532 1027 1368 1772 2169 2560 2956
6 1350 1924 2846 4109 932 1214 1534 1977 2380 2762
7 1615 2446 3619 831 1118 1402 1718 2169 2573
3 1320 1727 2517 3625 1224 1577 1938 2333 2732 3052
4 1579 2195 3245 4448 1010 1405 1767 2168 2547 2929
11 5 1392 1927 2852 4083 885 1179 1584 1990 2373 2757
6 1647 2465 3613 788 1074 1361 1770 2186 2570
7 1450 2098 3155 684 976 1260 1547 1966 2373
3 1566 2149 3149 1047 1407 1753 2136 2529 2883
4 1412 1901 2800 4012 841 1226 1598 1984 2356 2741
12 5 1669 2433 3580 744 1027 1402 1794 2177 2561
6 1466 2117 3142 642 932 1213 1574 1999 2385
7 1789 2710 529 831 1118 1402 1768 2189
3 1405 1850 2730 863 1233 1584 1945 2329 2717
4 1669 2375 3535 698 1037 1422 1780 2172 2545
13 5 1502 2104 3103 600 885 1206 1604 2003 2374
6 1824 2691 491 788 1072 1382 1808 2195
7 – – – 1544 2317 359 684 976 1260 1564 2004
NB: Values of capacity in bold face refer to nominal value.
Values of sensible capacity higher than values of total capacity mean that cooling is without dehumidification. In this case consi-
der only the values of sensible capacity.