EasyManuals Logo

AERMEC NRGI User Manual

AERMEC NRGI
32 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #19 background imageLoading...
Page #19 background image
19
6 RECOVERY MENU
6.1 ENABLING RECOVERY
WARNING: this mask is available on units with total recovery.
This mask is used to display the actual status of the total recovery, and to enable or
disable the total recovery:
YES
Switch On:
O General
The mask displays the total recovery status;the available options are:
ow switch open (water is not circulating in the hydraulic circuit of the recovery
system and therefore it is disabled);
enabled (water is circulating in the hydraulic circuit of the recovery system and
therefore it is enabled);
general o (whole unit in stand-by);
o from display (general disabling of the unit from the pGD1 button);
Enable: allows to enable or disable the total recovery;
6.2 SET THE RECOVERY SET VALUE
WARNING: this mask is available on units with total recovery.
This mask allows to view and set the value to be assigned to the recovery work set
(default value 45° C, setting range 30~50° C):
Setpoint 1:
45.0°C

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the AERMEC NRGI and is the answer not in the manual?

AERMEC NRGI Specifications

General IconGeneral
BrandAERMEC
ModelNRGI
CategoryHeat Pump
LanguageEnglish

Related product manuals