9 LIST OF ALARMS
There are three types of alarm resets:
Auto: automatic, when the event causing the alarm stops, also the alarm disappears.
Manual: manual, to restart normal operation manual acknowledgement is necessary.
Semi-auto: semi-automatic, the alarm is automatic but if it is present more than “n times, it then becomes manual. The interventions are decreased by one unit every hour.
Furthermore, there is a “timeout”, after which the alarm becomes manual, even if the maximum number of interventions is reached.
Code Description Reset Interventions Timeout(s)
AL01 Clock battery at alarm Auto
AL02 pCO memory error alarm Auto
AL03 Phase monitor alarm Semi-auto 3 300
AL04 Display alarm reset
AL09 Evaporator 1 input faulty probe alarm Manual 1
AL10 Evaporator 1 output faulty probe alarm Manual 1
AL11 Common evap. output faulty probe alarm Manual 1
AL16 Outside temperature faulty probe alarm Manual 1
AL17 Coil 1 temperature faulty probe alarm Semi-auto 5 60
AL19 Compressor maintenance request Auto
AL22 Evap pump maintenance request Auto
AL23 Circ. 1 compressor 1 technical alarm Manual 1
AL24 Evaporator 1 pump thermal alarm Manual 1
AL25 Evaporator 2 pump thermal alarm Manual 1
AL28 Ventilation unit 1 thermal alarm Manual 1
AL29 Circuit 1 fan thermal series Semi-auto 3 3600
AL30 Circ. 1 low pressure switch alarm Manual 1
AL31 Circ. 1 low pressure alarm Manual 1
AL32 Circ. 1 high pressure switch alarm Manual 1
AL33 Circ. 1 high pressure alarm Manual 1
AL34 Circ. 1 serious low pressure alarm Manual 1
AL38 Evaporator ow switch alarm Manual 1
AL40 Evaporator anti-freeze alarm Manual 1
AL41 Common evap. anti-freeze alarm Manual 1
AL42 Low water content force o alarm Auto
AL47 Dierential pressure fault transducer alarm Manual 1
AL48 Air-water envelope alarm Semi-auto 5 3600
AL49 Low overheating alarm Semi-auto 3 300
AL60 Circ. 1 leak detector alarm Manual 1
AL74 Circ. 1 comp. 1 discharge gas high temp. alarm Manual 1
AL75 Circ. 2 comp. 1 discharge gas high temp. alarm Manual 1
AL85 System high temperature Manual 1
AL86 SAC storage tank probe faulty Auto
AL87 Master oine Auto
AL88 Slave oine Auto
AL89 Incorrect master/slave SW version Auto
AL91 Slave alarm summary Auto
AL102 Water inlet temp. out of operating limits Manual 1
AL103 Coil 2 temperature faulty probe alarm Semi-auto 5 60
AL105 PEC Oine Semi-auto 20 60
AL106 PEC Software - alarm set 1
AL107 PEC Software - alarm set 2
AL108 PEC Hardware - alarm set 1
AL109 PEC Hardware - alarm set 2
AL110 Inverter drive - Drive fault 1
AL111 Inverter drive - Drive fault 2
AL112 Inverter drive - Drive fault 3
AL113 Inverter drive - Drive fault 4