AES 7788 Series RF Subscriber Unit Installation and Operation Manual
AES Corporation 33 40-7788, Rev 6, August 30, 2016
4.5 Set Modes Enable Repeating and Suppress AC Fail
HandHeld Programmer: <Ctrl> + <F4> PC Terminal: <i>
There are several functions that can be programmed in the Set Modes programming
area. Repeating can be disabled and AC Fail Reporting can be suppressed.
To Start, press programmer keys <CTRL> + <F4> (hold down the Control and the
F4 keys at the same time). The following message appears:
SET MODES--OLD: NEW
ENABLE RPTNG-Y: .
Enter Y to enable repeating capability. Default is Y.
Press <ENTER> then the following appears:
SPRSS ACFAIL -N: .
Enter Y/yes to suppress the reporting of AC Fail messages, enter N/no (the default
and setting required in UL installations) to disable the feature and allow normal
reporting of AC Fail messages. Default is N.
After <ENTER> then the following appears:
SPRSS CHRGFLT-N: .
Enter Y for yes to suppress the reporting of Charger Fault messages, enter N for no
(the default and setting required in UL installations) to disable the feature and allow
normal reporting of Charger Fault messages. Default is N.
After <ENTER> then the following appears:
SPRSS GNDFLT-N: .
Enter Y for yes to suppress the reporting of Ground Fault messages, enter N for no
(the default and setting required in UL installations) to disable the feature and allow
normal reporting of Charger Fault messages. Default is N.
Press <ENTER>, If data has been entered correctly, the following message appears:
OK
If the programming in this function is not completed within 65 seconds the function
will time-out. The Programmer will beep and the following message will be
displayed:
TIMEOUT
Refer to Section 4.3 - Timing Parameters, for information on and programming the
AC Reporting Delay that determines when the AC Fail is reported after it is detected.
Reporting AC Fail is normally a very important message and should not be
suppressed. UL installations require this setting to be set at “N”.
4.6 Reset RAM
Use the Reset RAM function to return the 7788F to the factory default settings. All
parameters except the Unit ID and Cypher code are returned to default values.
It is good practice to perform this function on a new factory unit to ensure that you
are always starting from the same configuration. Also perform this function if this is