5.3.1 Conditions for the DC Connection
The connected PV modules must meet following requirements
Same type
Same number
Identical alignment
Identical tilt
The following limit values at the DC input of the inverter must not be exceeded
(connecting to a higher voltage will destroy the device):
Anyhome
Maximum input voltage
Maximum input current
HNS1000TL-1
450V
6A
HNS1500TL-1
450V
8A
HNS2000TL-1
500V
12A
HNS2500TL-1
500V
14A
HNS3000TL-1
550
17A
HNS3600TL-1
550
18A
HNS4000TL-1
550
20A
5.3.2 Assembling the DC Plug Connector
In order to connect to the inverter, all connection cables of the PV modules must be
equipped with the DC plug connectors provided. You will find the necessary DC plug
connector for DC connection in the delivery.
To assemble the DC plug connectors, proceed as detailed below. Ensure the plug
connectors have the correct polarity. The whole connector will include the male side
and female side as showed below.