29 / 34
Over temperature
protection
1. The external conditions, such as
the PV voltage and the sunlight,
change too sharply.
The inverter restores automatically.
Restart the inverter; if the error still remains after repeated restarting,
please contact our after-sales.
When the grid returns to normal, the inverter restores automatically.
2. Ratings of the grid-side switch
do not meet the grid requirements
so that the switch has tripped.
3. AC connectors are in poor
connect.
Reconnect the connectors again.
Restart the inverter; if the error still remains after repeated restarting,
please contact our after-sales.
When the grid returns to normal, the inverter restores automatically.
2. Ratings of the grid-side switch
do not meet grid requirements so
that the switch has tripped.
3. AC connectors are in poor
connect.
Reconnect the connectors again.
Restart the inverter; if the error still remains after repeated restarting,
please contact our after-sales.
When the grid returns to normal, the inverter restores automatically.