EasyManua.ls Logo

Allen-Bradley 1734-OBV2S

Allen-Bradley 1734-OBV2S
235 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
216 Rockwell Automation Publication 1734-UM013N-EN-P - September 2017
Appendix F I/O Assemblies
Output Assemblies
Analog Input Assemblies
Table 27 - 1734-OB8S Input Assemblies
Instance
Decimal (hex)
Connection
Type
Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
580 (244 h) Safety and
Standard
0Safety Output 7
Status
Safety Output 6
Status
Safety Output
5 Status
Safety Output
4 Status
Safety Output
3 Status
Safety Output
2 Status
Safety Output
1 Status
Safety Output
0 Status
1028 (404 h) Safety and
Standard
0Safety Output 7
Status
Safety Output 6
Status
Safety Output
5 Status
Safety Output
4 Status
Safety Output
3 Status
Safety Output
2 Status
Safety Output
1 Status
Safety Output
0 Status
1Safety Output
Monitor 7
Safety Output
Monitor 6
Safety Output
Monitor 5
Safety Output
Monitor 4
Safety Output
Monitor 3
Safety Output
Monitor 2
Safety Output
Monitor 1
Safety Output
Monitor 0
1044 (414 h) Safety and
Standard
0Safety Output
Monitor 7
Safety Output
Monitor 6
Safety Output
Monitor 5
Safety Output
Monitor 4
Safety Output
Monitor 3
Safety Output
Monitor 2
Safety Output
Monitor 1
Safety Output
Monitor 0
1 Reserved Combined
Output Status
Reserved Output Power
Error
(1)
Reserved
(1) This data is diagnostic only and does not have safety integrity.
Table 28 - 1734-OBV2S Input Assemblies
Instance
Decimal (hex)
Connection
Type
Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
579 (243 h) Safety 0 Reserved Reserved Reserved Reserved Safety Output
3 Status
Safety Output
2 Status
Safety Output
1 Status
Safety Output
0 Status
1027 (403 h) Safety and
Standard
0Safety Output 3
Readback
Safety Output 2
Readback
Safety Output
1 Readback
Safety Output
0 Readback
Safety Output
3 Status
Safety Output
2 Status
Safety Output
1 Status
Safety Output
0 Status
1043 (413 h) Safety and
Standard
0 Reserved Reserved Reserved Reserved Safety Output
3 Readback
Safety Output
2 Readback
Safety Output
1 Readback
Safety Output
0 Readback
1 Reserved Combined
Output Status
Reserved Output Power
Error
(1)
Reserved
(1) This data is diagnostic only and does not have safety integrity.
Table 29 - Output Assemblies for all POINT Guard I/O™ Modules
Instance Decimal
(hex)
Module Connection
Type
Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
33 (21 h) 1734-IB8S Safety
(1)
0
Reserved
Standard
Output 3
Standard
Output 2
Standard
Output 1
Standard
Output 0
564 (234 h) 1734-OB8S Safety Only 0 Safety
Output 7
Safety
Output 6
Safety
Output 5
Safety
Output 4
Safety
Output 3
Safety
Output 2
Safety
Output 1
Safety
Output 0
563 (233 h) 1734-OBV2S Safety Only 0 Reserved Reserved Reserved Reserved Safety
Output 3
Safety
Output 2
Safety
Output 1
Safety
Output 0
770 (302 h) 1734-IE4S Safety 0 Reserved Reserved Reserved Reserved Reset Tach
3
(2)
Reset Tach
2
(2)
Reset Tach
1
(2)
Reset Tach
0
(2)
(1) Only outputs 1 and 3 are configurable to Muting or Test Outputs. This assembly is accessible only over a Safety connection.
(2) When set (1), this bit specifies a reset of an overfrequency condition on the tachometer counter. Clear this bit to allow the tachometer channel to operate.
Table 30 - 1734-IE4S Input Assemblies
Instance
Decimal (hex)
Connection
Type
Byte High Byte Low Byte

Table of Contents