214 Logical Instructions
OR - Logical OR
Instruction Type: output
The OR instruction performs a logical OR of two sources and places the
result in the destination.
OR
Bitwise Inclusive OR
Source A N7:0
0000h<
Source B N7:1
0000h<
Dest N7:2
0000h<
OR
Execution Time for the OR Instruction
Controller Data Size When Rung Is:
True False
MicroLogix 1100 word 13.06 μs 0.84 μs
long word 13.31 μs 0.84 μs
Truth Table for the OR Instruction
Destination = A OR B
Source: A
1111101000001100
Source: B
1100111111000011
Destination:
1111111111001111
IMPORTANT
Do not use the High Speed Counter Accumulator
(HSC.ACC) for the Destination parameter in the AND,
OR, and XOR instructions.